hmi/¶
The hmi/ directory holds declarative HMI pages, SVG process boards, trends,
alarms, and write policy.
Typical Layout¶
hmi/
_config.toml
overview.toml
trends.toml
alarms.toml
plant.toml
plant.svg
drive-cell.toml
views/
drive-cell.topology.toml
drive-cell.view.toml
Important Files¶
| File | Purpose |
|---|---|
_config.toml |
global HMI settings, refresh, theme, write policy |
overview.toml |
dashboard-style operator page |
trends.toml |
trend widgets and time-series views |
alarms.toml |
alarm list / acknowledgement view |
<page>.toml |
page definition with widgets or process bindings |
<page>.svg |
process artwork referenced from kind = "process" pages |
views/<name>.topology.toml |
human/AI-authored 3D component topology source |
views/<name>.view.toml |
static 3D scene payload referenced from kind = "scene3d" pages |
Write Policy¶
[write]¶
| Key | Type | Required | Notes |
|---|---|---|---|
enabled |
bool | yes | Enables runtime-side writes from the HMI. |
default_role |
string | yes | Default role for write-capable actions. |
allowlist |
string array | yes | Explicit symbol allowlist. |
| policy_mode | enabled |
default_role |
allowlist |
Example |
|---|---|---|---|---|
| read-only | false |
viewer |
[] |
alarms/trends only |
| controlled writes | true |
operator |
explicit symbol list | start/stop buttons, setpoints |
Minimal read-only policy:
[write]
enabled = false
default_role = "viewer"
allowlist = []
Controlled write policy:
[write]
enabled = true
default_role = "operator"
allowlist = [
"PROGRAM PumpStation.PumpSpeed",
"GLOBAL Control.StartButton",
]
Process Pages¶
Process pages bind live symbols to SVG selectors:
title = "Plant"
kind = "process"
svg = "plant.svg"
[[bind]]
selector = "#pump_state"
attribute = "class"
source = "PROGRAM PumpStation.Run"
map = { "true" = "running", "false" = "stopped" }
[[bind]]¶
| Key | Type | Required | Notes |
|---|---|---|---|
selector |
string | yes | SVG/CSS selector to target. |
attribute |
string | yes | Attribute to update. |
source |
string | yes | Runtime symbol path. |
map |
table | no | Value-to-attribute mapping. |
3D Scene Pages¶
Scene pages reference a compiled view payload under hmi/views/ and keep live
tag bindings in the page descriptor:
title = "Drive Cell 3D"
kind = "scene3d"
topology = "drive-cell.topology.toml"
view = "drive-cell.view.toml"
[[bind3d]]
node = "motor-1.shaft"
property = "transform.rotation.y"
source = "Main.shaft_angle"
scale = { min = -3.14159265, max = 3.14159265, output_min = -3.14159265, output_max = 3.14159265 }
The loader resolves view = "drive-cell.view.toml" to
hmi/views/drive-cell.view.toml. View payload files are not page descriptors.
Topology Sources¶
hmi/views/<name>.topology.toml is the normal human and AI authoring source for
3D pages. The topology compiler emits the .view.toml file used by the runtime
and writes a generated header containing the topology source hash.
[[components]]
id = "TK-101"
kind = "tank"
at = { grid = "A1" }
[[components]]
id = "P-101"
kind = "pump"
at = { grid = "A3" }
[[connections]]
id = "line-101"
from = "TK-101.outlet"
to = "P-101.inlet"
medium = "water"
diameter = "DN50"
route = "auto"
[[bindings]]
component = "TK-101"
signal = "level"
source = "Program.TK101.level"
access = "read"
[[interactions]]
component = "P-101"
event = "click"
action = "hmi.write"
id = "resource/RESOURCE/program/Main/field/run"
value = true
required_role = "Engineer"
confirmation = { title = "Start pump", message = "Write Main.run TRUE" }
The built-in v1 component library ships with tank, pump, valve, motor,
vfd, and transmitter kinds. Each kind defines ports, domains, default
primitive visuals, and signal-to-bind3d mappings. The compiler validates
component kinds, ports, domains, grid uniqueness, raw-coordinate justification,
binding signal names, and write interaction role safety before emitting the
view payload.
View Payloads¶
P1 view payloads can define primitive scene nodes, cameras, lights, and
low-level bind3d records:
[[node]]
id = "motor-1.shaft"
primitive = "box"
[node.transform]
position = [0.0, 0.0, 0.0]
rotation = [0.0, 0.0, 0.0]
scale = [1.0, 0.35, 0.35]
[node.material]
base_color = "#3b82f6"
[[node.interaction]]
event = "click"
action = "hmi.write"
id = "resource/RESOURCE/program/Main/field/run"
value = true
required_role = "Engineer"
confirmation = { title = "Start motor", message = "Write Main.run TRUE" }
[[camera]]
id = "main"
position = [0.0, 0.0, 4.0]
target = [0.0, 0.0, 0.0]
[[light]]
id = "key"
kind = "directional"
intensity = 1.0
The P1 runtime bridge renders primitive nodes through scena. Asset-backed
nodes remain a later trust-twin slice.
[[node.interaction]]¶
Compiled scene nodes can expose operator interactions. P3 supports hmi.write
only, and the runtime/webview route that request through the same control
endpoint, role policy, allowlist, parser, pending-write queue, and audit path
used by 2D HMI writes.
| Key | Type | Required | Notes |
|---|---|---|---|
event |
string | yes | click, touch, or toggle. |
action |
string | yes | hmi.write in P3. |
id |
string | yes | HMI write target id/path passed as params.id. |
value |
bool/string/number | yes | Value passed as params.value. |
required_role |
string | yes | Must be Engineer; lower roles are rejected by policy. |
confirmation |
table | no | title and message metadata for operator confirmation. |
[[bind3d]]¶
| Key | Type | Required | Notes |
|---|---|---|---|
node |
string | yes | Scene node id to target. |
property |
string | yes | One of the bounded 3D property names. |
source |
string | yes | Runtime symbol path, validated like 2D HMI bindings. |
map |
table | no | Value-to-property mapping. |
scale |
table | no | Numeric input/output scaling. |
Supported P1 properties are visible, transform.position,
transform.position.x, transform.position.y, transform.position.z,
transform.rotation.x, transform.rotation.y, transform.rotation.z,
transform.scale, transform.scale.x, transform.scale.y,
transform.scale.z, material.base_color, material.emissive,
material.opacity, and text.value.
Lifecycle Commands¶
Use: