Networking And Remote Access

Good questions for this page:

  • which endpoints need to be reachable?
  • which ones should stay loopback-only?
  • what firewall/TLS/token policy should I enforce?

Guide

PLC Networking & Remote Access

This guide explains which ports are used and how to enable remote access safely.

Default ports

  • Web UI: 8080 (HTTP)
  • Discovery: mDNS (UDP 5353)
  • Mesh/data: 5200 (TCP/UDP as configured)
  • MQTT broker (if any configured I/O driver is mqtt): 1883 (TCP, broker-defined)

Local‑only by default

trueST ships in local‑only mode by default. To enable remote access:

  1. Enable a TCP control endpoint in runtime.toml.
  2. Set runtime.control.auth_token (required for TCP).
  3. Use the pairing flow in the Web UI to share access.

Firewall checklist

  • Allow inbound TCP 8080 for Web UI (if remote web access is required).
  • Allow UDP 5353 for discovery (LAN only).
  • Allow TCP/UDP 5200 if mesh is enabled.
  • Allow TCP 1883 only when MQTT integration is explicitly enabled.
  • VPN (WireGuard or OpenVPN)
  • SSH tunnel for Web UI

TLS for remote endpoints

When exposing web/control endpoints beyond localhost, enable TLS explicitly.

Example runtime.toml settings:

[runtime.web]
enabled = true
listen = "0.0.0.0:8080"
auth = "local"
tls = true

[runtime.tls]
mode = "self-managed"
cert_path = "security/server-cert.pem"
key_path = "security/server-key.pem"
require_remote = true

Rules enforced by runtime schema:

  • runtime.web.tls=true requires runtime.tls.mode != "disabled".
  • TLS-enabled mode requires runtime.tls.cert_path and runtime.tls.key_path.
  • if runtime.tls.require_remote=true and web listen is remote, TLS must be enabled.

Troubleshooting

If remote access fails: - Check that the PLC is reachable by IP. - Verify firewall rules. - Confirm runtime.control.auth_token is set for TCP control.