If the plant question is about emergency stop handling, e-stop boundaries, safe state, restart discipline, or commissioning sign-off, start here.

E-Stop And Safe-State Boundary

This page covers e-stop handling, emergency stop boundaries, safe state behavior, restart discipline, and commissioning sign-off.

Guide

truST PLC Safety Guide

This guide explains how the runtime handles faults, watchdogs, and safe-state outputs. It is not a substitute for a site-specific safety assessment.

1) Safe State Outputs

Define safe outputs in the Web UI (I/O → I/O configuration → Safe‑state outputs), or directly in io.toml, so the runtime can force them on fault/watchdog:

[[io.safe_state]]
address = "%QX0.0"
value = "FALSE"

When a fault occurs, outputs are driven to these values before halting.

2) Watchdog Behavior

Watchdog monitors cycle/task execution time. If the timeout is exceeded: - Resource transitions to FAULT - Outputs go to safe state - Execution halts until restart

Example:

[runtime.watchdog]
enabled = true
timeout_ms = 5000
action = "safe_halt"

3) Fault Policy

Faults include divide-by-zero, out-of-bounds access, invalid type conversion, FOR step of 0, and deadline overruns.

Set policy in runtime.toml:

[runtime.fault]
policy = "halt"

4) Retain + Restart

Warm restart restores RETAIN variables. Cold restart resets all values.

Use warm restarts for controlled recovery. Use cold restarts after wiring changes or if state is uncertain.

5) Debug in Production

Debug attach is disabled by default in production. Only enable in controlled maintenance windows.

runtime.control.mode = "production"
runtime.control.debug_enabled = false

6) Operator Checklist

Before commissioning: - Verify safe-state outputs. - Trigger a test fault and confirm outputs go safe. - Confirm watchdog timeout and restart behavior. - Confirm retain persistence for required values.

During operation: - Monitor status and fault events. - Restart cold if safety is uncertain.