Ladder Diagram

Related: truST ladder profile, Develop -> Ladder

Ladder Diagram (LD) Language Specification

IEC 61131-3 Edition 3.0 (2013-02) - Section 8.2 (Ladder Diagram)

Status: Normative language specification for LD behavior in this repository.

1. Purpose and Scope

This document defines the normative Ladder Diagram (LD) language semantics used by truST. It covers:

  • LD program model (networks/rungs and power flow).
  • Variable usage rules in LD.
  • Contact/coil/branch behavior.
  • Function and function block invocation in LD bodies.
  • Deterministic scan-cycle evaluation model.
  • Required diagnostics for invalid LD programs.

This document is implementation-agnostic. JSON/webview/runtime profile constraints are defined separately in docs/specs/16-ladder-profile-trust.md.

2. Conformance Language

The keywords MUST, MUST NOT, SHOULD, SHOULD NOT, and MAY are normative.

An implementation conforms to this specification only if all MUST requirements in this document are satisfied, except where an explicit deviation is recorded in docs/IEC_DEVIATIONS.md.

3. IEC Anchors Used

Primary IEC anchors used by this LD specification:

  • IEC 61131-3 Ed.3 Section 8.2: Ladder Diagram (LD)
  • IEC 61131-3 Ed.3 Table 40: FUNCTION_BLOCK declarations
  • IEC 61131-3 Ed.3 Tables 43-46: standard FB semantics (bistable, edge, counter, timer)
  • IEC 61131-3 Ed.3 Section 6.5.2.2 and Figure 7: variable sections and visibility

4. LD Program Model

4.1 Networks and Execution Order

  • An LD body consists of ordered networks (rungs).
  • Networks are evaluated from top to bottom in deterministic order.
  • Each network is evaluated from logical left rail toward logical right rail.

4.2 Power Flow

  • Power flow within a network is boolean.
  • A path is energized when all series conditions on that path evaluate true.
  • Parallel branch paths are independent logical alternatives.

4.3 Determinism

The implementation MUST define deterministic tie-break behavior when source layout is ambiguous (for example, equal horizontal positions or partially disconnected geometry).

5. Variable and Data Model

5.1 Symbolic-First Policy

LD programs SHOULD be authored with symbolic variables declared in IEC variable sections, including:

  • local declarations (VAR, VAR_TEMP, VAR_INPUT, VAR_OUTPUT, VAR_IN_OUT)
  • global declarations (VAR_GLOBAL)
  • global access via VAR_EXTERNAL

Directly addressed operands (%I, %Q, %M) MAY be used when required for hardware binding, but they are secondary to symbolic declarations.

5.2 Scope and Resolution

Variable resolution in LD MUST respect IEC scope rules:

  1. local/POU scope
  2. enclosing context scope (where applicable)
  3. global scope via VAR_EXTERNAL
  4. qualified names

5.3 Type Requirements

  • Contact conditions MUST resolve to BOOL-compatible values.
  • Coil targets MUST be assignable BOOL-compatible storage locations.
  • Compare and math block operands MUST satisfy their operator type requirements.
  • Timer/counter instance typing MUST satisfy the corresponding standard FB contract.

6. Core LD Element Semantics

6.1 Contacts

  • NO contact passes power when its operand evaluates true.
  • NC contact passes power when its operand evaluates false.

6.2 Coils

  • NORMAL: writes current network power to target.
  • SET: when powered, writes TRUE; when unpowered, leaves previous value unchanged.
  • RESET: when powered, writes FALSE; when unpowered, leaves previous value unchanged.
  • NEGATED: writes logical negation of current network power to target.

6.3 Branching

  • Branch split duplicates incoming power to outgoing branch legs.
  • Branch merge resolves incoming leg power by logical OR.
  • Branch evaluation MUST be deterministic and independent of rendering artifacts.

7. Functions and Function Blocks in LD

7.1 Function Invocation

Functions used in LD boxes MUST follow the same type and parameter rules as ST expression calls.

7.2 Function Block Invocation

Function block instances used in LD MUST follow IEC FB declaration and call contracts (Table 40 and relevant FB tables).

7.3 Standard FB Semantics

When these blocks are supported in LD, semantics MUST align with IEC standard tables:

  • Bistable FBs: Table 43
  • Edge detection FBs: Table 44
  • Counters: Table 45
  • Timers: Table 46

If a subset profile is implemented, unsupported FB behavior MUST be diagnosed and listed in docs/IEC_DEVIATIONS.md.

8. Scan-Cycle Execution Semantics

An LD scan MUST follow this sequence:

  1. Acquire input image.
  2. Evaluate networks in deterministic order.
  3. Compute writes during evaluation.
  4. Commit writes at defined commit boundary.
  5. Publish resulting state for next cycle/observation.

To preserve deterministic PLC behavior, write effects from one network SHOULD NOT create hidden intra-cycle order dependence beyond the defined commit model.

9. Diagnostics and Error Conditions

Implementations MUST emit actionable diagnostics for at least:

  • unresolved variable references
  • invalid or non-assignable coil targets
  • type-incompatible element operands
  • malformed network topology (for graph-based editors/importers)
  • unsupported LD constructs in interchange formats

Diagnostics SHOULD identify the element/network and expected contract.

Diagnostic Area Expected message focus
unresolved references identify the missing symbol and the network element that referenced it
invalid coil target state that the target is not assignable and name the offending coil
type mismatch identify the LD element and incompatible operand types
malformed topology identify the broken branch/network structure
unsupported interchange construct identify the PLCopen/import/export construct that was rejected

10. Edition 2 vs Edition 3 Compatibility

For LD core behavior (contacts, coils, branching, and scan-cycle interpretation), this spec adopts IEC Edition 3 as authoritative and maintains behavior compatible with Edition 2 usage patterns.

Known incompatibilities or profile restrictions MUST be recorded in docs/IEC_DEVIATIONS.md.

11. Examples

11.1 Symbolic Global + Local Mapping

VAR_GLOBAL
  StartPB : BOOL;
  StopPB  : BOOL;
  Motor   : BOOL;
END_VAR

PROGRAM Main
VAR_EXTERNAL
  StartPB : BOOL;
  StopPB  : BOOL;
  Motor   : BOOL;
END_VAR

Equivalent LD intent:

  • NO(StartPB) in series with NC(StopPB) drives NORMAL(Motor).

11.2 Direct Address Form (Optional)

  • NO(%IX0.0) in series with NC(%IX0.1) driving NORMAL(%QX0.0).

This form is allowed for direct hardware binding but is not the preferred modeling style.

12. Profile Boundary

The concrete truST LD profile (JSON schema, VS Code editor behavior, runtime panel wiring, interop subset, and current limitations) is specified in:

  • docs/specs/16-ladder-profile-trust.md

Any profile-specific behavior that differs from this normative document MUST be tracked in:

  • docs/IEC_DEVIATIONS.md