Comm

Comm gives the program and the HMI the state of every communication link the runtime runs: connected, degraded or failed, since when, the last data and the latest error, with an alarm and the link faceplate.

Library Guide

The Comm library gives the program and the HMI the state of every communication link the runtime runs: an io.toml driver (Modbus TCP, MQTT, EtherCAT, GPIO, simulated, loopback), an ADS client connection or an OPC UA client connection. The program declares a Link block naming its link; the runtime fills the block's outputs at the start of every scan. The program uses them to stop equipment safely when a link fails, and the operator opens the link faceplate to see which link failed, since when and why. The contract is specification 42, docs/specs/42-communication-links.md.

Package Setup

[project]
include_paths = ["src"]

[dependencies]
Alarm = { path = "../../libraries/alarm", version = "0.1.0" }
Comm = { path = "../../libraries/comm", version = "0.1.0" }

The block's alarm comes from the Alarm library, so a project adds both. The program writes USING Comm;.

Design Rules

  • One Link per link, called once per scan with the link's Name.
  • The runtime writes the outputs at the start of each scan, after the inputs are read and before the program runs. The program reads them and never writes them.
  • A block first called with its Name in one scan is filled from the next scan; until then it reads Unknown.
  • The program decides what a failed link means for the process (interlocks, safe state, holding the last value); the block's alarm tells the operator.

A link's name is the identity Devices & Connections uses:

Link Name
an io.toml driver <protocol>:<position>, its position in io.toml from 0: modbus_tcp:0, mqtt:1, ethercat:0, gpio:0, simulated:0, loopback:0
an ADS client connection ads:<connection>, for example ads:line
an OPC UA client connection opcua_client:<connection>, for example opcua_client:plant

Blocks

Block Use Faceplate Symbol
Link the state of one link, filled by the runtime, with its alarm link network-link

Common Types

LinkState:

State Meaning
Unknown the runtime runs no link of that name, or has not read it yet
Connecting the link is being established
Connected data is exchanged
Degraded data is exchanged with problems, for example stale or bad values
Failed no data is exchanged
Disabled the link is configured but switched off

A driver is Connected while healthy, Degraded while degraded and Failed while faulted, with the driver's error text. An ADS or OPC UA client connection is Degraded while any of its points is degraded, and Failed while it reconnects or has faulted.

Interface Summary

Link   Name, AlarmDelay (10 s), Enable (TRUE), Test, Reset
       -> State, Connected, Disabled, Known, StateTime, LastGoodAge, LastError,
          Exchanges, Failures, ResponseTime, TestResult, Detail; alarm LinkFailed
  • State is the link's state, a LinkState.
  • Connected is TRUE while data is exchanged: Connected or Degraded.
  • Disabled is TRUE while the link is switched off on purpose, by Enable or in its configuration.
  • Known is FALSE when the runtime runs no link of that name; LastError then says so.
  • StateTime is how long the link has been in its state; LastGoodAge how long ago data was last exchanged, 0 while it is.
  • LastError keeps the latest error after the link recovers.
  • LinkFailed is a Medium alarm, "<Name> failed", raised when no data has been exchanged for AlarmDelay: the link failed, its name is unknown to the runtime, or it never finished connecting. A link switched off on purpose (Disabled) raises none; LastError tells the causes apart.
  • Enable FALSE switches an io.toml driver's link off from the next scan: the runtime neither reads nor writes the driver, so the program keeps the last input values and the device the last outputs. The link reads Disabled and raises no alarm. One block with Enable FALSE is enough. ADS and OPC UA client connections are switched in their configuration; Enable does not reach them.
  • A rising edge of Test reads the driver once into a spare image, which the program does not see, and writes the outcome to TestResult: "answered in 12 ms", or the error. A client connection is not tested this way, and TestResult says so.
  • Exchanges counts the scans in which data was exchanged, Failures the scans in which the link was Failed. A rising edge of Reset sets both to 0 for every block of the link.
  • ResponseTime is how long an io.toml driver's last read and write took; 0 for a client connection, which exchanges in the background.
  • Detail is the protocol's own state in its words: a Modbus TCP server and unit and its last exception reply, an MQTT broker and session, what EtherCAT discovery found, a GPIO chip and its lines; an ADS client connection's summary or an OPC UA client connection's session detail. Empty when the protocol reports none.
  • An input the program's call passes is the program's each scan; the faceplate's switches work on the inputs the call leaves out.

Operating From The HMI

Place the network-link symbol, bind its connected to the block's Connected and its out-of-service to Disabled, and give it [object.click] faceplate = "link". A link switched off on purpose then reads Off, out of service, not lost. The link faceplate shows the link's name, its state and how long it has been in it, whether data is exchanged and when it last was, its latest error, its exchanges, failures and response time, its protocol's own state, and its alarm. For engineers it has Link on (Enable), Test link (Test, with TestResult under it) and Reset counters (Reset); only an engineer may use them. Everything else on it is the runtime's.

The runtime writes them only within its write policy ([[runtime.web.hmi.write]] in runtime.toml), for example:

[[runtime.web.hmi.write]]
path = "Main.RemoteIo.Enable"
role = "engineer"

[[runtime.web.hmi.write]]
path = "Main.RemoteIo.Test"
role = "engineer"

[[runtime.web.hmi.write]]
path = "Main.RemoteIo.Reset"
role = "engineer"

Examples

A transfer pump stops when the link to its remote I/O fails:

USING Comm;

PROGRAM Transfer
VAR
    RemoteIo : Link;
    StartRequest : BOOL;
    PumpRun : BOOL;
END_VAR
    RemoteIo(Name := 'modbus_tcp:0', AlarmDelay := T#5s);
    PumpRun := StartRequest AND RemoteIo.Connected;
END_PROGRAM

A line that keeps the last good value of a remote measurement while its OPC UA link is down, and says how old it is:

USING Comm;

PROGRAM Line
VAR
    Plant : Link;
    RemoteFlow : LREAL;
    Flow : LREAL;
    FlowAge : TIME;
END_VAR
    Plant(Name := 'opcua_client:plant');
    IF Plant.State = LinkState#Connected THEN
        Flow := RemoteFlow;
    END_IF;
    FlowAge := Plant.LastGoodAge;
END_PROGRAM

A remote I/O station is taken off its link while it is serviced, with no alarm, and tested before it goes back:

USING Comm;

PROGRAM Station
VAR
    RemoteIo : Link;
    Servicing : BOOL;
    TestRequest : BOOL;
    Answer : STRING[120];
END_VAR
    RemoteIo(Name := 'modbus_tcp:0', Enable := NOT Servicing, Test := TestRequest);
    Answer := RemoteIo.TestResult;
END_PROGRAM

Validation

cargo test -p trust-runtime --test comm_links
cargo test -p trust-runtime --test comm_link_actions
cargo test -p trust-runtime --test comm_faceplates
cargo test -p trust-runtime --test comm_guide
cargo test -p trust-runtime --lib link_subsystem

comm_links drives a link through its states and checks an unknown name, a disabled driver and the alarm; comm_link_actions switches a driver's link off and on, tests it and checks its counters, their reset and its response time against a simulated device; comm_faceplates checks the pair and the faceplate against the library; comm_guide compiles and runs every example of this guide; the unit tests map every state of ADS and OPC UA client connections.