Alarm

Alarm is truST's alarm library: ISA-18.2 and EEMUA 191 alarms as function blocks that the runtime lists, shows in the runtime display, lets operators acknowledge, shelve and reset, and records in OpenOT.

Library Guide

The Alarm library defines alarms as function blocks, following ISA-18.2 (IEC 62682) and EEMUA 191. Every alarm is an instance in the program. The program calls it every scan and can use its outputs for horns, beacons and interlocks without any HMI. The truST runtime lists every alarm on its own, shows them in the runtime display, applies operator actions and records every transition. The contract is specification 40, docs/specs/40-alarm-library.md.

Use the detection blocks for the usual cases: a condition, a limit, a deviation, or a command its feedback does not follow. Extend the base block when your alarm needs its own detection; it then gets the whole lifecycle, the records and the display.

Package Setup

[project]
include_paths = ["src"]

[dependencies]
Alarm = { path = "../../libraries/alarm", version = "0.1.0" }

The program writes USING Alarm;. The Plant library uses this library for the alarms of its blocks, so a project with Plant already has it.

Design Rules

  • One instance per alarm, called once in every scan with its inputs.
  • The alarm's identity is its instance path, for example Tank.LevelHigh. The alarm list, the records and the OpenOT history name it so; the HMI files hold no alarm definitions.
  • Three priorities, High, Medium and Low: most alarms Low, few High. A trip is not a priority: the alarm that caused it is a High alarm marked first out, and the trip itself is an event. Information is never an alarm; the program sends it as an OpenOT message record.
  • Operator actions reach the alarm through its Request member, which the alarm applies in its next scan and then clears. The program uses the methods Acknowledge (a local push button) and Reset (a latched alarm).
  • Declared in a VAR RETAIN section, an alarm keeps its state, its shelving and its out-of-service mark across a warm restart; otherwise it starts Normal.
  • A value that is not finite counts as beyond a limit: a broken measurement is not hidden.
  • Blocks that hold alarms, such as the Plant library's motors and valves, hold them as members (P101.FailedToStartAlarm), so the display shows each alarm on its equipment.

Blocks

Block Extends Active while
Alarm the base: lifecycle, message, priority, delays, latching, shelving, suppression by design, out of service, first out; own detection calls its protected method Evaluate(Condition)
DigitalAlarm Alarm Condition is TRUE
LimitAlarm Alarm High: from Value > Limit until Value < Limit - Deadband; Low: from Value < Limit until Value > Limit + Deadband
DeviationAlarm Alarm from ABS(Value - Reference) > Limit until it is below Limit - Deadband
DiscrepancyAlarm Alarm Command <> Feedback; OnDelay is the time the equipment may take to follow
FirstOutGroup marks the first alarm of its group to become active, until the group is reset

Common Types

  • AlarmPriority: Low := 1, Medium := 2, High := 3.
  • AlarmState: Normal, ActiveUnacknowledged, ActiveAcknowledged, ClearedUnacknowledged.
  • LimitDirection: High, Low.
  • AlarmRequest: Acknowledge, Shelve (a duration), Unshelve, Reset, Comment, RemoveFromService, ReturnToService; written by the runtime for an operator's action.

Lifecycle

From Event To
Normal the condition becomes active (after OnDelay) ActiveUnacknowledged
ActiveUnacknowledged acknowledged ActiveAcknowledged
ActiveUnacknowledged the condition clears (after OffDelay), not latching ClearedUnacknowledged
ActiveAcknowledged the condition clears, not latching Normal
ClearedUnacknowledged acknowledged Normal
ClearedUnacknowledged the condition becomes active again ActiveUnacknowledged
  • An alarm that clears before it is acknowledged stays listed until it is acknowledged.
  • RaiseCount grows by one each time the alarm becomes active.
  • Shelved by an operator for 1 s to 24 h, the alarm does not annunciate and needs no acknowledgement, but its condition is still followed. It returns by itself when the time ends, or when an operator unshelves it, as ActiveUnacknowledged if its condition holds.
  • Suppressed by design while the program's Suppressed input is TRUE (for example the low-flow alarm of a stopped pump), and out of service while an engineer has taken it out for maintenance: in both cases it does not annunciate and returns as from shelving.
  • Latching: the alarm stays active after its condition clears, until Reset() or an operator's reset, which take effect only once the condition is gone.
  • First out: of the alarms whose Group refers to one FirstOutGroup, the first to become active after the group's last Reset() has FirstOut TRUE until the group is reset again.

Interface Summary

Alarm             Message, Priority (Low), OnDelay (0 s), OffDelay (0 s), Latching, Suppressed,
                  Group (REF_TO FirstOutGroup)
                  -> Active, Unacknowledged, State, Shelved, OutOfService, SuppressedByDesign,
                     FirstOut, Annunciating, RaiseCount
                  METHOD Acknowledge; METHOD Reset; METHOD PROTECTED Evaluate(Condition)
DigitalAlarm      Condition
LimitAlarm        Value, Limit, Deadband (0), Direction (High)
DeviationAlarm    Value, Reference, Limit, Deadband (0)
DiscrepancyAlarm  Command, Feedback
FirstOutGroup     -> Epoch; METHOD Reset; METHOD Join : UDINT (used by the alarms)

Annunciating is TRUE while the alarm is active or unacknowledged and not shelved, suppressed or out of service: the output for a horn or a beacon.

Operating From The HMI

The runtime display shows the alarms without any HMI file:

  • the top bar's counter of annunciating alarms, in the mark and colour of the highest priority, blinking while any is unacknowledged, and beside it the newest alarm;
  • the alarm list: unacknowledged first, then by priority, then newest first; shelved, suppressed and out-of-service alarms listed apart with their counts, never hidden without a trace;
  • on each symbol, the mark of its equipment's annunciating alarms, which opens the alarm;
  • the event log of alarm transitions, operator actions and command outcomes.

High is a red diamond, Medium an orange triangle and Low a yellow circle, each with "!".

Action Role Request field
Acknowledge Operator Acknowledge
Shelve for a duration (1 s to 24 h) Operator Shelve
Unshelve Operator Unshelve
Reset a latched alarm Operator Reset
Comment Operator Comment
Out of service Engineer RemoveFromService
Back in service Engineer ReturnToService

Each action needs an HMI session with the role, goes to the audit log with the user's name, and is confirmed when the alarm shows it applied. The library defines the actions and their roles, so the runtime's write policy needs no entry for them. With [runtime.openot] enabled, every transition is published as an OpenOT condition record; those records are the alarm history.

Examples

Level limits of a tank, high and high-high, each with its own priority:

USING Alarm;

PROGRAM Tank
VAR
    Level : LREAL;
END_VAR
VAR RETAIN
    LevelHigh : LimitAlarm;
    LevelHighHigh : LimitAlarm;
    LevelLow : LimitAlarm;
END_VAR
    LevelHigh(Value := Level, Limit := 85.0, Deadband := 2.0,
        Message := 'Tank T-101 level high', Priority := AlarmPriority#Medium);
    LevelHighHigh(Value := Level, Limit := 95.0, Deadband := 2.0, OnDelay := T#2s,
        Message := 'Tank T-101 level high-high', Priority := AlarmPriority#High);
    LevelLow(Value := Level, Limit := 10.0, Deadband := 2.0, Direction := LimitDirection#Low,
        Message := 'Tank T-101 level low');
END_PROGRAM

A pump that does not start within 5 s of its command, with a horn and a local acknowledge button:

USING Alarm;

PROGRAM Pumps
VAR
    StartCommand AT %QX0.0 : BOOL;
    RunningFeedback AT %IX0.0 : BOOL;
    AcknowledgeButton AT %IX0.1 : BOOL;
    Horn AT %QX0.1 : BOOL;
END_VAR
VAR RETAIN
    FailedToStart : DiscrepancyAlarm;
END_VAR
    FailedToStart(Command := StartCommand, Feedback := RunningFeedback, OnDelay := T#5s,
        Message := 'Pump P-101 failed to start', Priority := AlarmPriority#High);
    IF AcknowledgeButton THEN
        FailedToStart.Acknowledge();
    END_IF;
    Horn := FailedToStart.Annunciating AND FailedToStart.Unacknowledged;
END_PROGRAM

The first cause of a boiler trip: each trip alarm latches and joins one group; the reset button resets the alarms and starts a new first out:

USING Alarm;

PROGRAM Boiler
VAR
    FlameLost AT %IX0.0 : BOOL;
    WaterLow AT %IX0.1 : BOOL;
    PressureHigh AT %IX0.2 : BOOL;
    ResetButton AT %IX0.3 : BOOL;
    Burner AT %QX0.0 : BOOL;
    Trips : FirstOutGroup;
END_VAR
VAR RETAIN
    Flame : DigitalAlarm;
    Water : DigitalAlarm;
    Pressure : DigitalAlarm;
END_VAR
    Flame(Condition := FlameLost, Latching := TRUE, Group := REF(Trips),
        Message := 'Boiler flame lost', Priority := AlarmPriority#High);
    Water(Condition := WaterLow, Latching := TRUE, Group := REF(Trips),
        Message := 'Boiler water low', Priority := AlarmPriority#High);
    Pressure(Condition := PressureHigh, Latching := TRUE, Group := REF(Trips),
        Message := 'Boiler pressure high', Priority := AlarmPriority#High);
    IF ResetButton THEN
        Flame.Reset();
        Water.Reset();
        Pressure.Reset();
        Trips.Reset();
    END_IF;
    Burner := NOT (Flame.Active OR Water.Active OR Pressure.Active);
END_PROGRAM

A temperature that strays from its setpoint, suppressed while the heater is off:

USING Alarm;

PROGRAM Oven
VAR
    Temperature : LREAL;
    Setpoint : LREAL := 180.0;
    HeaterOn : BOOL;
END_VAR
VAR RETAIN
    TemperatureDeviation : DeviationAlarm;
END_VAR
    TemperatureDeviation(Value := Temperature, Reference := Setpoint, Limit := 10.0,
        Deadband := 2.0, OnDelay := T#1m, Suppressed := NOT HeaterOn,
        Message := 'Oven temperature away from setpoint');
END_PROGRAM

Own detection: a pump running dry. The block extends the base and calls Evaluate with its condition; message, priority and delays are the base's inputs:

USING Alarm;

FUNCTION_BLOCK DryRunAlarm EXTENDS Alarm.Alarm
VAR_INPUT
    Running : BOOL;
    Flow : LREAL;
    MinimumFlow : LREAL := 1.0;
END_VAR
    Evaluate(Condition := Running AND Flow < MinimumFlow);
END_FUNCTION_BLOCK

PROGRAM Station
VAR
    PumpRunning : BOOL;
    Flow : LREAL;
END_VAR
VAR RETAIN
    DryRun : DryRunAlarm;
END_VAR
    DryRun(Running := PumpRunning, Flow := Flow, OnDelay := T#10s,
        Message := 'Pump P-101 running dry', Priority := AlarmPriority#High);
END_PROGRAM

Validation

cargo test -p trust-runtime --test alarm_library
cargo test -p trust-runtime --test web_hmi_alarms
cargo test -p trust-runtime --test openot_alarm_records
cargo test -p trust-runtime --test alarm_guide

alarm_library runs the lifecycle of specification 40 on the blocks, web_hmi_alarms the alarm list and the operator actions of the runtime display, openot_alarm_records the history, and alarm_guide compiles and runs every example of this guide.